A meat processor in the Midlands partnered with SMARTech energy for refrigeration energy savings across its cold stores and blast freezers. In the first eight weeks, with only the first measures in place, the site used 23% less electricity, at no upfront cost.
A managed service, not just a fit-out
This is a managed service. Our team doesn't install equipment and walk away: we manage the savings, watch how the site's plant is operating day to day, and keep finding ways to optimise it, so the savings keep improving over time.
No capital expenditure. We fund, install and maintain the measures.
Shared savings. The client's payments come from a share of the verified savings.
Better profitability. Lower energy bills go straight to the bottom line.
Lower carbon emissions and maintenance costs. Plant that runs less hard uses less energy and wears less.
23%less electricity in the first eight weeks
£0upfront cost to the client
4hidden plant faults found by monitoring
At a glance
ClientMeat processor, Midlands
SiteProduction Monday to Friday; refrigeration running 24/7 and using about three-quarters of the site's electricity
ContractEnergy Efficiency as a Service: a managed service with no upfront cost
Measures so farSMART Factory refrigeration and blast freezer controls, power optimisation and remote monitoring
Still to comeFurther measures as the project progresses
VerificationIPMVP, adjusted for production, weather and non-working days
The challenge
Production stops at the weekend, but the cold stores, blast freezers and refrigerated containers keep going, so refrigeration drives most of the electricity bill.
Units were running colder than they needed to.
There was no overall energy strategy or monitoring, so nobody could see where energy was being used or wasted.
Savings would be hard to prove. The site's plant was changing during the project, and any result had to stand up to scrutiny.
Refrigeration runs around the clock and uses about three-quarters of the site's electricity.
What we did
Understood the site first. Detailed, remote, minute-by-minute monitoring of energy and temperature showed us where the energy was going. We combined it with 16 months of meter data, weather and production to build a fair baseline that every saving is measured against.
Made targeted changes. Our SMART Factory controls make sure each cold store and freezer works only as hard as it needs to. Smart blast freezer controls optimise when and how they run, and power optimisation makes better use of the site's incoming supply.
Monitored every circuit. Our monitoring records the main meter and each refrigeration circuit separately, so we can see how every cold store and freezer is behaving, not just the site total.
Kept the measurement honest. When the client replaced or added plant, we measured each change and adjusted the baseline for it. Equipment failures are taken out too, so the reported saving reflects only what our measures achieved.
Refrigeration energy savings: the results
Across the first eight weeks, the site used 23% less electricity than it would have done without the changes, verified to IPMVP, and the savings grew as each measure took effect.
Verified savings so far, and our projection for the first year. Stage 1 is verified to IPMVP; Stage 2, from January 2027, is a projection as further measures come in.
Stage 1 covers the measures in place now, with savings of 23% verified to IPMVP. Stage 2 adds further measures from January 2027, and we expect savings to rise to around 33%. We'll verify those results in the same way as they come in.
The monitoring also found four problems the site didn't know about:
A cold store refrigeration system had been tripped for over four months. We spotted it and the client reset it.
A newly installed freezer unit had iced up, pushing up that cold room's energy use by around 30% until it was repaired.
Settings had drifted over time. Adjustments made on busy days weren't always set back. We brought them back in line with the site team.
A refrigerated container stopped with a fault, which we confirmed so the client could chase the hire company.
Circuit-level monitoring shows each cold store and freezer separately.
What's next
These results come from the first reconciliation period, September to October 2026. Further measures are still to come, and we'll update this case study once we have a full year of verified results.
It all starts with understanding your site's energy: what is being used, where, and where it's being wasted. We'll look at your bills and tell you honestly what you could save. With Energy Efficiency as a Service (opens in a new tab), there's nothing to pay upfront.
SMARTech energy® delivered a highly successful commercial Solar PV upgrade and expansion at JSP Ltd’s Worsham Mill site, transforming a non‑functional legacy system into a high‑performing renewable energy asset.
By combining detailed energy analytics, selective reuse of existing infrastructure, and intelligent system redesign, the project now achieves close to 100% on‑site self‑consumption, minimal grid export, and an estimated 4‑year simple payback with a ~500% lifetime ROI over 20 years.
This project demonstrates how underperforming or ageing Solar PV systems can be upgraded into revenue‑generating assets that materially reduce operating costs, protect against energy price volatility, and support long‑term sustainability goals.
The Client challenge
JSP Ltd had invested previously in Solar PV, but the original system was no longer operational. This created several business risks:
Loss of on‑site renewable generation
No meaningful return on earlier capital investment
Rising exposure to grid electricity prices
Lack of performance visibility or actionable data
Negatively impacting client trust in technology
The requirement was not a like‑for‑like replacement, but a solution that maximised value from existing assets while delivering long‑term commercial performance.
The SMARTech approach
SMARTech energy® adopted a data‑led, asset‑optimisation strategy rather than a full strip‑out and replacement. Key elements of the solution included:
Detailed load analysis using historic monitoring data to accurately match generation to site demand
Selective decommissioning of non‑performing legacy arrays
Retention of viable infrastructure where performance remained acceptable
Installation of higher‑efficiency PV modules to replace underperforming sections
Expansion across multiple roof orientations (N‑W, S‑E and S‑W) to extend daily generation profiles
Export limitation in full compliance with G99/G100 requirements
Deployment of remote monitoring for real‑time performance tracking and optimisation
This approach ensured the system was correctly sized, avoided costly overspecification, and maximised on‑site utilisation of generated electricity.
System overview
Total installed capacity: 346.62 kWp
Inverters: 5 × Solis commercial inverters
Grid compliance: Export limitation in line with DNO requirements
Warranties: Long‑term manufacturer warranties on panels and inverters
The final design delivers consistent generation throughout the working day, aligning production closely with operational demand.
Measured performance
Live monitoring data confirms that the system is exceeding expectations.
July – December 2025:
Modelled generation: 130,774 kWh
Actual generation: 139,740 kWh
Performance vs prediction: 107%
Several months significantly outperformed forecast output, validating both the system design and commissioning quality.
Financial results
The financial performance has exceeded projections by a substantial margin.
July – December 2025:
Predicted import cost avoidance: £23,933
Actual import cost avoidance: £32,912
Electricity unit rate: ~£0.23/kWh
With export kept deliberately low, the system prioritises self‑consumption, delivering maximum financial benefit directly to the business.
Environmental impact and strategic benefits
Significant reduction in grid‑supplied electricity
Measurable reduction in associated carbon emissions
Direct contribution to JSP Ltd’s sustainability and Net Zero objectives
Improved resilience against future energy price volatility
Value delivered to the Client
Immediate and verifiable reduction in electricity costs
Recovery and extension of value from existing solar assets
Transparent performance data via remote monitoring
Long‑term operational visibility and optimisation capability
A future‑proofed renewable energy platform
Why this matters for other businesses
This project demonstrates that commercial Solar PV success is not just about installing more panels. The real value lies in:
Correct system sizing
Intelligent reuse of existing assets
High on‑site self‑consumption
Verified, data‑backed performance
SMARTech energy® delivers Solar PV solutions that perform as financial assets, not just sustainability statements.
Upgrade or optimise your Solar PV
Already have Solar PV on site?
Whether your system is underperforming, ageing, or no longer operational, SMARTech energy® can assess, upgrade, and optimise your installation to deliver measurable commercial returns.
Energy management in hotel achieves 33.34% energy savings for the Burnham Beeches Hotel
The Burnham Beeches Hotel in Buckinghamshire has achieved 33.34% combined energy savings from their gas and electricity through an energy management partnership with SMARTech energy.
Measured and verified energy reduction results to manage and reduce their energy consumption, costs and carbon, reveal energy savings of 33.34% in year 2 of the program and a predicted reduction in carbon emissions of 1,560 Tonnes over the term of the contract.
SMARTech energy’s partnership with the Burnham Beeches Hotel (a part of the Corus Hotels Group) is now in its second year of a 10-year Energy Efficiency as a Service programme.
This partnership has delivered measured and verified results averaging 31.2% combined gas & electricity savings from the first 2 years – which will save the hotel energy, money and carbon.
With three commercial options available, Burnham Beeches took the zero CapEx, shared savings approach to an energy efficiency programme. This option requires no investment from the client, and they typically receive 30% of the savings.
Through this model, It’s enabled the hotel to execute a fully-funded energy efficiency programme with SMARTech energy managing the strategy to design, integrate, install and deliver a comprehensive portfolio of efficient building technologies – from LED lighting, insulation, SMART refrigeration to 97% efficiency boiler systems.
Throughout the 10-year programme, SMARTech energy are responsible for maintenance and warranty of the technology and proving the energy savings year-on-year.
GUARANTEED ENERGY SAVINGS THROUGH A TRUSTED, MANAGED PARTNERSHIP
Energy Consultancy
An initial site survey and discussion of opportunities to reduce the site’s energy consumption, enabled SMARTech energy’s team of expert consultants and engineers to design an energy monitoring system and install it. This gives minute by minute data to help understand the site usage profiles across various equipment and loads on site.
Monitoring
The data analytics produced from this, then helped to form the basis of an energy reduction report. Through factual data, it’s this report which focuses on preventing energy wastage and provides recommendations for improvements, either through updates to energy efficient technologies or changes to process.
Energy Consultancy – Strategy Report
The Strategy Report details and provides reasoning on areas where energy savings can be achieved, such as settings, setpoints, scheduling and control systems. It’s this report which is fundamental to achieving the goals of the programme and for the measurement and verification process to be fully realised.
Installation
The installation by our team of electricians and engineers of the recommended energy conservation measures (ECMs), guarantees to reduce energy consumption and optimises the energy performance and operating conditions across the site.
Tech Stack
The long-term energy reduction strategy with the Burnham Beeches Hotel includes (but is not limited to) LED lighting upgrades, motor optimisation, SMART refrigeration, energy efficient boilers, thermal insulation jackets and gas savers.
Project Management
Continuous project management of the energy reduction programme ensures the success of all elements of the partnership; including management support, energy monitoring, plus through the use of visuals from powerful dashboard analytics – which provide alerts and which continue to guarantee results.
IPMVP – Monitoring and Verification
Energy savings are measured and verified using an internationally recognised Performance, Measurement and Verification Protocol (IPMVP). This protocol is used to measure and validate the performance of energy management and reduction calculations.
First Year Savings report:
End of year one of the EEaaS programme
Combine energy savings 29% (Gas & Electricity)
The reporting period for the measurement and verification (M&V) analysis is from 1st June 2021 to 31st May 2022 for both gas and electricity. The independent variables applied to gather this data included heating degree days at 15.5 ̊C (HDD15.5) and number of sleepers (sleeper) in each respective month (delegate numbers). The data for weather related independent variable (HDD) was collected from the website www.degreedays.net, which was stipulated in the M&V plan.
Second Year Savings report:
End of year two of the EEaaS programme
Combine energy savings 33.34% (Gas & Electricity)
The following graph provides a visual understanding of the electrical and gas energy savings realised at the site and represents an average from the savings achieved over the past 2 years. The top line of the graph represents the adjusted baseline energy usage of kWhs – if upgrades to low-carbon technologies were not carried out. The bottom line on the graph is the actual measured energy usage on utility bills following technology upgrades. These energy savings are measured and verified using an international protocol (IPMVP).
Two years combined average savings for both gas and electric equates to 31.2%
Ongoing Support
On-going support of Burnham Beeches’ energy management strategy ensures that the site’s energy performance and operating conditions are optimised. This support guarantees continuous energy savings.
IT Support
Energy dashboards provide our customers with a real-time reporting tool which tracks the effects of energy saving efforts.
This information allows SMARTech energy’s consultancy team to constantly analyse and optimise technologies at the site.
Manage
Managing a client’s energy reduction strategy on a long-term partnership leads to guaranteed, proven and measured ongoing energy savings.
The savings achieved through this energy management partnership demonstrates the hotel’s commitment to innovation, sustainability and best practice towards environmental policy; ensuring the site ultimately, save energy, save money and save carbon.
Wiltshire-based SMARTech energy partnered with UTC Swindon to reduce their energy consumption, costs and carbon through its Energy Efficiency as a Service (EEaaS) programme.
Measured and verified energy reduction results reveal average energy savings over 2 years of 30.46%. This reduction will also avoid more than 671 tonnes of CO2 emissions over the terms of the contract.
SMARTech energy developed a comprehensive energy reduction strategy to achieve these savings and with the EEaaS partnership now in it’s third year of a 10 year programme, this is set to help the college to save energy, save money and save carbon.
With three commercial options available, SMARTech energy have made reducing energy consumption and going green very simple.
UTC Swindon took the zero CapEx, shared savings approach to energy efficiency. It’s where the energy savings pay for the installation and maintenance of low-carbon technology products – enabling organisations to implement an energy reduction drive and improve costs, carbon and sustainability. There’s no upfront costs, leasing or risk and the client typically receives 30% of the savings.
Through this model, its enabled the UTC to execute a fully-funded energy efficiency programme with SMARTech energy managing the strategy to design, integrate, install and deliver a comprehensive portfolio of efficient building technologies – from LED lighting, base load reduction and motor optimisation.
Throughout the 10 year programme, SMARTech energy will be responsible for managing the technologies and proving the energy savings year on year.
GUARANTEED ENERGY SAVINGS THROUGH A TRUSTED, MANAGED PARTNERSHIP
Energy Consultancy
An initial site survey and discussion of opportunities to reduce the site’s energy consumption, enabled SMARTech energy’s team of expert consultants and engineers to design an energy monitoring system and install it. This gives minute by minute data to help understand the site usage profiles across various equipment and loads on site.
Monitoring
The data analytics produced from this, then helped to form the basis of an energy reduction report. Through factual data, it’s this report which focuses on preventing energy wastage and provides recommendations for improvements, either through updates to energy efficient technologies or changes to process.
Energy Consultancy – Strategy Report
The Strategy Report details and provides reasoning on areas where energy savings can be achieved, such as settings, setpoints, scheduling and control systems. It’s this report which is fundamental to achieving the goals of the programme and for the measurement and verification process to be fully realised.
Installation
The installation by our team of electricians and engineers of the recommended energy conservation measures (ECMs), guarantees to reduce energy consumption and optimises the energy performance and operating conditions across the site.
Tech Stack
The long-term energy reduction strategy with UTC Swindon includes (but is not limited to) LED lighting upgrades, motor optimisation and baseload reduction.
Project Management
Continuous project management of the energy reduction programme ensures the success of all elements of the partnership; including management support, energy monitoring, plus through the use of visuals from powerful dashboard analytics – which provide alerts and which continue to guarantee results.
IPMVP – Monitoring and Verification
Energy savings are measured and verified using an internationally recognised Performance, Measurement and Verification Protocol (IPMVP). This protocol is used to measure and validate the performance of energy management and reduction calculations.
First M&V Savings report:
End of year one of the EEaaS programme
Energy savings 43%
Carbon savings 1.976 Tonnes
The measurement period for the first measurement and verification analysis was from 1st July 2021 to 30th November for electricity. The independent variables are heating degree days (HDD) and cooling degree days (CDD) for each month for the AHU. No independent variables were used for the LED lighting, with a sample based analysis approach employed.
Second Year Savings report:
End of year two of the EEaaS programme
Energy savings 33%
Carbon savings 23.5 Tonnes
The independent variables applied are heating degree days at 18 ̊C, cooling degree days at 15.5 ̊C and school hours. The data for two weather related independent variables were collected from the website www.degreedays.net as stipulated in the M&V plan. The independent variables on school hours is calculated based on the term time schedule available on the school’s website.
Third Year Savings report:
End of year two of the EEaaS programme
Energy savings 28.2%
Carbon savings 46 Tonnes
The independent variables were based on the same variables as above.
Combined average for electric savings equates to 30.46%
The following graph provides a visual understanding of the electrical energy savings realised at the site and represents an average from the savings achieved over the past 2 years. The top line of the graph represents the adjusted baseline energy usage of kWhs – if upgrades to low-carbon technologies were not carried out. The bottom line on the graph is the actual measured energy usage on utility bills following technology upgrades. These energy savings are measured and verified using an international protocol (IPMVP).
Ongoing Support
On-going support of UTC Swindon’s energy management strategy ensures that the site’s energy performance and operating conditions are optimised. This support guarantees continuous energy savings.
IT Support
Energy dashboards provide our customers with a real-time reporting tool which tracks the effects of energy saving efforts.
This information allows SMARTech energy’s consultancy team to constantly analyse and optimise technologies at the site.
Manage
Managing a client’s energy reduction strategy on a long-term partnership leads to guaranteed, proven and measured ongoing energy savings. UTC Swindon is one of more than 40 education sites within the Activate Education Trust.
SMARTech energy’s management partnership with UTC Swindon follows the successful roll out of the Energy Efficiency as a Service (EEaaS) programme at other UTC sites across the country.
The savings achieved through this energy management partnership demonstrates the Trust’s commitment to improving sustainability, costs and carbon across the group.
UNIVERSITY TECHNICAL COLLEGE (UTC) READING ACHIEVE 30% ENERGY REDUCTION
Measured and verified energy reduction results from SMARTech energy’s partnership with the University Technical College (UTC) Reading to manage and reduce their energy consumption, costs and carbon, reveal energy savings of 30% and a projected reduction in carbon emissions of 220 Tonnes over the term of the contract.
SMARTech energy partnered with UTC Reading through it’s Energy Efficiency as a Service (EEaaS) programme. This partnership guarantees to save the UTC 30% – which will save energy, save money and save carbon.
With three commercial options available, UTC Reading took the zero CapEx, shared savings approach to an energy efficiency programme. This requires no investment from the client and the client typically receives 30% of the savings.
They didn’t have the capital to invest or the knowledge and resource to implement an energy reduction plan and wanted to upgrade their site with innovative building technologies.
SMARTech energy therefore provided 100% of the investment to develop a strategy to design, integrate, install and deliver a comprehensive portfolio of energy efficient technology upgrades – which have been designed to achieve the most efficient energy savings.
Throughout the 10 year programme, SMARTech energy will be responsible for managing the technologies and proving the energy savings year on year.
Energy Consultancy
An initial site survey and discussion of opportunities to reduce the site’s energy consumption, enabled SMARTech energy’s team of expert consultants and engineers to design an energy monitoring system and install it. This gives minute by minute data to help understand the site usage profiles across various equipment and loads on site.
Monitoring
The data analytics produced from this, then helped to form the basis of an energy reduction report. Through factual data, it’s this report which focuses on preventing energy wastage and provides recommendations for improvements, either through updates to energy efficient technologies or changes to process.
Energy Consultancy – Strategy Report
The Strategy Report details and provides reasoning on areas where energy savings can be achieved, such as settings, setpoints, scheduling and control systems. It’s this report which is fundamental to achieving the goals of the programme and for the measurement and verification process to be fully realised.
Installation
The installation by our team of electricians and engineers of the recommended energy conservation measures (ECMs), guarantees to reduce energy consumption and optimises the energy performance and operating conditions across the site.
Tech Stack
The long-term energy reduction strategy with UTC Reading includes (but is not limited to) LED lighting upgrades, voltage optimisation on the site’s main incoming energy supply and motor optimisation of variable speed drives (VSDs).
Project Management
Continuous project management of the energy reduction programme ensures the success of all elements of the partnership; including management support, energy monitoring, plus through the use of visuals from powerful dashboard analytics – which provide alerts and which continue to guarantee results.
IPMVP – Monitoring and Verification
Energy savings are measured and verified using an internationally recognised Performance, Measurement and Verification Protocol (IPMVP). This protocol is used to measure and validate the performance of energy management and reduction calculations.
The following graph provides a visual understanding of the electrical energy savings realised at the site. The top line of the graph represents the adjusted baseline energy usage of kWhs – if upgrades to low-carbon technologies were not carried out. The bottom line on the graph is the actual measured energy usage on utility bills following technology upgrades. These energy savings are measured and verified using an international protocol (IPMVP).
Ongoing Support
On-going support of the UTC’s energy management strategy ensures that the site’s energy performance and operating conditions are optimised. This support guarantees continuous energy savings.
IT Support
Energy dashboards provide our customers with a real-time reporting tool which tracks the effects of energy saving efforts.
This information allows SMARTech energy’s energy consultancy team to constantly analyse and optimise technologies at the site.
Manage
UTC Reading is one of more than 40 education sites within the Activate Learning Education Trust.
SMARTech energy’s management partnership with UTC Reading follows the successful roll out of the Energy Efficiency as a Service (EEaaS) programme at other UTC sites across the country – and where our specialist consultancy team have helped to achieve energy savings in consumption, costs, and carbon.
Managing a client’s energy reduction strategy on a long-term partnership enables SMARTech energy’s expert energy consultancy team to guarantee, prove and measure ongoing energy savings.
SMARTech energy are pleased to positively and proactively help the Activate Learning Education Trust to make change to improve sustainability across the group.
CONTACT US
Call our team on 01225 635 660 for more information on this case study and how we can help your business or organisation. [sdfile id=”64012″]
Let SMARTech energy define and design the right solution for you
Energy savings of more than 73% with C02 reduction of 91 tonnes per year.
THE CLIENT
The Adelphi Group of Companies supply a wide range of packaging & processing machinery and equipment to a number of different industries.
THE CHALLENGE
Based in Haywards Heath, The Adelphi Group’s main production and stores area is situated on a mezzanine floor and with heat rising from the warehouse below, it has made the temperature too warm and uncomfortable to work in during the summer months.
Due to the large open space, evaporative cooling systems were recommended – as the running costs of traditional air conditioning would have proved too expensive*.
* Even on the very hottest summer days the evaporative cooling systems will supply fresh air cooling at temperatures below 23C at typically less than 10% of the operating costs of refrigeration
As an authorised installer of Evaporative Cooling systems for UK manufacturer, EcoCooling Ltd, SMARTech energy were brought on board to design in an energy efficient cooling system at the site – with the aim to improve the working environment for their staff.
Prior to the project start, a team from The Adelphi Group were invited to visit our previous evaporative cooling installation work at the Herman Miller factory site in Wiltshire, to better understand the installation process of evaporative cooling.
THE SOLUTION
2 x Evaporative cooling systems with recirculation capability. Both controlled via single PLC
Cooled air is discharged to the area by 2 x fabric ducts running the length of the production area
2 x nozzles in the ends of the duct direct more air to the mezzanine area
Hot air is removed via 2 x exhaust grilles located above the supply entry points
Low energy usage – automatically ramps up and down according to needs. Fresh air injection into working areas for operatives
BENEFITS OF EVAPORATIVE COOLING
Improves security – as would not need to leave doors open to introduce cooler air in summer
The external units are roof mounted so require no floor or external space for installation
All work can be carried out during business hours and does not require any downtime
The cooling solution will improve the working environment for its staff and deliver energy savings to the company
Acting as a recirculation system for winter and a ventilator or evaporative cooling system for the summer
Even on the very hottest summer days the Evaporative Cooling systems will supply fresh air cooling at temperatures below 23C at typically less than 10% of the operating costs of refrigeration
THE RESULTS
SMARTech energy were approached in late 2019 and work to a schedule that would take advantage of a quieter period in The Adelphi Group’s production; thereby allowing SMARTech energy to install the system with minimal disruption to daily operations and more importantly, have the air cooling systems functioning prior to the summer months.
The project was led by Head of Evaporative Cooling at SMARTech energy Seth Robinson.
Seth comments “The installation took a team of 3 engineers, 2 weeks to install and we are delighted with the finished project. We will continue to maintain and service all of the units and our relationship with The Adelphi Group continues to thrive”.
For more information on this case study, please contact us on 01225 653 660 or via the website contact us page.